This product meets IEC 298, GB

| project | unit | data | |
| Rated voltage | kV | 3.6、7.2、12 | |
| Rated insulation level | 1min power frequency withstand voltage | kV | 24、32、42 |
| Lightning impulse withstand voltage | kV | 40、60、75 | |
| Rated frequency | Hz | 50 | |
| Rated current | A | 630、1250、1600、2000、2500、3150 | |
| Rated thermal stable current (effective value/s) | kA | 25/4、31.5/4、40/3 | |
| Rated dynamic stable current (peak value) | kA | 63、80、100 | |
| Protection level | Enclosure IP4X, circuit breaker door opens to IP2X | ||
| project | Dimensions/weight | |
| Height (mm) | The rated current of the branch bus reaches 1250A | 2300(2200) |
| Width (mm) | Thermal stable current 31.5kA | 800(650) |
| The rated current of the branch bus is above 1600A | 1000 | |
| Depth(mm) | Cable entry and exit | 1300、1500 |
| Overhead entrance and exit lines | 1660 | |
| Weight (kg) | 800~1200 | |

Phone
0086-13868724314
Phone